Control valve common failure analysis and solutions

Time:2021-03-26
The control valve is widely used in oil refining and chemical industry. It is used to control the flow rate, pressure and liquid level of the fluid in the production process...

The control valve is widely used in oil refining and chemical industry. It is used to control the flow rate, pressure and liquid level of the fluid in the production process.In the application of control valves, calculation and selection is the premise, installation and debugging is the key, use and maintenance is the purpose.If the selection of the control valve is not appropriate, improper installation or debugging is not good, it will not play a regulating role.Therefore, it is very important to be familiar with the control valve working principle and maintenance skills.

Principle of control valve

Pneumatic control valve to compressed air as power source, through the cylinder, film as the actuator, and with the help of electrical valve positioner, converter, solenoid valve, position valve and other accessories, to achieve switching or continuous adjustment, receiving DCS control signals to adjust the medium flow, pressure, temperature and other process parameters.Pneumatic valve is mainly divided into two types of gas open type and gas closed type, characterized by simple control, quick response, essential safety, no need to use explosion-proof measures.

Control valve failure mode and cause

The main failure forms of pneumatic control valve are: the internal leakage valve does not act, the opening degree fluctuates greatly, the jam phenomenon appears, the operation is normal but the flow rate does not change.The main reasons are: valve body fault, cylinder fault, locator fault, DCS fault, control cable fault, maintenance is not in place, valve quality problems, selection or design reasons, pneumatic components fault.

01. Valve body failure and countermeasures

Common faults

    1) The metal valve seat of the butterfly valve is damaged and the valve body is stuck;The butterfly valve fixing bolt falls off or the connecting bolt between the spool and the stem of the half ball valve slides. The main performance is that the spool appears to have acted but the spool does not act

    2) Internal wear of the ball valve body causes the valve to be easily stuck or the valve to act slowly;Damaged ball valve soft seal gasket causes valve to leak or get stuck.

    3) The damage of the shaft sleeve of the half ball valve causes the valve to operate difficult.

    4) steam leakage caused by high temperature aging of steam valve stem seal;The steam valve muffler falls off, causing the valve to often get stuck and the pipe to be unusually noisy.

    5) Internal leakage caused by wear or corrosion of valve stem;Damaged seal at stem packing resulting in leakage.

The reason countermeasures

    1) the cause of the spool valve seat leakage is the surface wear or corrosion of the spool valve seat, the actuator force is too small, and the valve seat thread is worn and loosened.Troubleshooting: improve the grinding joint surface, adjust the actuator and stem connection, tighten bolts or replace the spool seat.

    2) The cause of leakage between the seat ring and the valve body is that the tightening torque is too small, the surface finish of the valve body is poor, the gasket is not suitable, and the valve body has small holes or burrs.Fault treatment: increase the twisting force, clean and treat the valve body again, replace the appropriate gasket, and weld the valve body again.

    3) the cause of packing leakage is that the stem finish is not good or bending, the packing cover is not pressed or the packing type is unreasonable, the packing layer is piled too high, the packing appears corrosion pit or the packing cover deformation and damage.Fault treatment: polish valve stem and press straight, tighten or replace packing;Install spacer ring, reduce height, replace with good performance packing, repair and replace gland and associated flange bolts, etc.

    4) The valve stem and the valve vibration cause the valve stem connection to break off or break, the reason is that the torque is too large, the pin connection is not appropriate.Fault treatment mode: use the valve core stem integral part or welded valve core to connect the connector firmly and eliminate the vibration factor.The cause of valve vibration is the leakage of sealing filler, the bypass is not adjusted well, the positioner gain is too high, and the vibration source is not well supported.Fault treatment: lubricate the packing and adjust, readjust the bypass, select the low-gain positioner, and fix the valve firmly to avoid the vibration source.

02. Causes and countermeasures of cylinder failure

Common faults

    1) The actuator limit bolt falls off, resulting in air leakage of the cylinder, which causes the valve to be unable to act or to act slowly, and can not reach the predetermined opening.

    2) The damage to the O-ring of the cylinder leads to air leakage, which makes the valve difficult to operate or unable to operate.

    3) the deformation of the cylinder piston leads to the increase of friction, and the loosening of the cylinder bolt causes the cylinder to leak, thus causing the valve to operate difficult.

    4) The linkage mechanism of the cylinder driving the valve body action is loose or rusted, resulting in difficult valve action.

    5) Small cylinder capacity or cylinder spring failure leads to difficult valve action.

The reason countermeasures

    1) The cause of the leakage at the piston seal is the poor smoothness of the cylinder;The sealing of piston ring assembly is not enough, the temperature of the sealing ring is too high, and the sealing parts are damaged for too long.Fault treatment: grind the cylinder and readjust the cylinder limit bolt, select the sealing ring again according to the use temperature, and install it correctly when replacing.

    2) The treatment of cylinder limit bolt loosening: tighten the bolt again.

    3) the treatment of large piston friction: re-lubricating oil, re-cleaning and grinding cylinder and piston.

    4) the valve action is difficult to reach the fixed stroke, the actuator spring value is not enough or the spring is damaged, the position of the limit block is not accurate.Treatment: calibrate, reschedule and replace the spring.

03. Locator Fault Causes and Countermeasures

Common faults

    1) The fault of the locator circuit board causes the abnormal action of the valve.

    2) The damage or wear of the small slide valve causes the abnormal action of the valve. The reason is that the air cleanliness of the instrument is not high, or dirt enters the positioner and causes the wear of the small slide valve, which causes the abnormal action of the valve.

    3) The damage of the proportional valve of the positioner causes abnormal valve action.

    4) The damage of sliding rheostat leads to inaccurate positioning of the valve and abnormal operation of the valve. The main reason is that the ambient temperature is too high and water and other liquids enter, which leads to the damage of the rheostat.

    5) The O-sealing ring of the air source interface of the positioner is broken, which causes the broken O-sealing ring to jam the stem of the small slide valve and make it unable to act.

    6) The sealing of the gran head of the locator is not good, which leads to the water damage of the locator circuit board.

    7) due to the pipeline vibration is too large, the surrounding environment temperature is too high, humidity is too large, cause the circuit board failure.

The reason countermeasures

    1) The seal problem at the glen head leads to the water inlet of the locator and causes the circuit board damage.Fault treatment: improve the sealing of the gran head, so as to avoid the damage of the circuit board caused by the water inside the locator.

    2) due to the instrument air humidity and more dust, leading to the small slide valve into the dirt caused by the small slide valve wear, so that the valve action is not normal.Trouble handling: add air filter to improve air quality of instrument.

    3) Frequent damage of sliding rheostat and circuit board is caused by excessive ambient temperature, humidity and vibration.Fault treatment: the circuit board and the small slide valve and slide rheostat separation, made of separated valve positioner.

    4) The O-ring of the positioner often breaks, leading to the stem of the small slide valve being stuck. The main reason is that the air source pressure is too large. Normally, it should be about 0.5Mpa, and higher than 0.5Mpa will lead to faster aging of the sealing ring and easy damage.Fault treatment: keep the air source pressure at about 0.4Mpa, and provide better quality sealing ring.

04. Failures caused by process and design and countermeasures

Common faults

    1) The valve cannot be operated due to the large pressure difference in pipeline caused by the change of process parameters.

    2) Scaling of the valve body caused by the medium causes abnormal valve action.

    3) The valve cannot operate normally due to pipeline blockage.

    4) Due to the design and selection reasons, the actuator is small, the torque is not enough, the valve can not operate normally, and the material of the valve body is not appropriate, leading to the damage of the valve body.

The reason countermeasures

    1) Excessive pressure difference causes the control valve to fail to open normally.Treatment: a bypass valve is installed before and after the control valve.

    2) The control valve can not be opened normally due to scaling of the valve body due to process reasons.Treatment: increase the flushing water pipe, in addition to regularly open the valve to clean the valve body, if necessary, grinding the valve core.

    3) The control valve can not operate due to pipeline blockage.Treatment method: optimize the operation method, as far as possible not to clog the pipeline, in addition to open the pipeline flushing valve.

    4) About the design selection.Treatment method: in the design stage, try to optimize a variety of process parameters, to ensure that selection will not cause problems due to inaccurate process parameters.

05. The fault caused by DCS and countermeasures

Common faults

    1) I/O card damage without signal output, resulting in the control valve can not operate.

    2) DCS output signal is unstable, resulting in the control valve opening fluctuation, so that the control valve action is not normal.

    3) the control cable is damaged or the insulation is not good, the wiring is loose and the signal is not normal, which causes the control valve to act abnormal.

    4) Because of the maintenance is not in place, the locator water, cylinder corrosion and air leakage, air source pipe sleeve fall off and air leakage and other reasons cause abnormal action of the control valve.

    5) Because the inspection is not careful, the hidden danger is not found in time, which leads to further expansion, and finally causes abnormal action of the control valve.

The reason countermeasures

    Daily maintenance and inspection should be done well, and hidden dangers should be dealt with in time.When the opening of the control valve fluctuates, timely check whether the PID parameters are set correctly and adjust the parameters in time.

06. Failure caused by damage of pneumatic components and countermeasures

Common faults

    1) The air supply pressure is low due to the aging and damage of the air supply hose or the leakage of the stainless steel air supply pipe, which makes the operation of the control valve abnormal.

    2) Abnormal action of control valve caused by air filter fracture or dirty filter element.

    3) Abnormal action of control valve caused by low air source pressure or closed air source.

The reason countermeasures

    1) replace the air source hose or air filter with better quality;If the air source hose or air filter is found to be damaged or leak during regular inspection, or the filter element is too dirty, it is necessary to find the opportunity to replace it as soon as possible.

    2) Adjust the air source pressure to meet the minimum air source pressure requirements of pneumatic valves.

主站蜘蛛池模板: 亚洲国产黄色片_秋霞久久久久久一区二区_国产自91精品一区二区_av高清播放资源_精品一区二区三区久久久_国产.精品.日韩.另类.中文.在线.播放_少妇人妻综合久久中文字幕888_色爱综合网 | 久久久久国产精品免费a片记大片_国产五月色婷婷六月丁香视频_亚洲人体一区二区_成人国产网址_51社区精品视频在线视频观看软件_日本一道高清_手机午夜看片_小箩莉h文徐韵婷合集小说 | 欧美一区免费在线观看_夭天干天天躁天天摸_k8久久久一区二区三区_又粗又大又硬毛片免费看_亚洲图片欧美小说_内射无码午夜多人_99久久免费国内精品_久久精品操 | 乱人伦人妻中文字幕不卡_蜜桃视频麻豆_99热久久是国产免费66_亚洲一级一区_色在线观看视频_欧美精品久久天天躁_香蕉欧美成人精品A∨在线观看_91.久久 | 亚洲欧美中文在线视频_国产的毛片_老司机av福利_久久伊人免费视频_无码毛片一级高潮免费视频_精品欧美久久久_亚洲第一狼人天堂久久_精品区2区3区4区产品乱码9 | 欧一区二区三区_色婷婷狠狠久久综合五月_国产国产成人久久精品_国产ts一区_日本一区二区三区乱码_狠狠操导航_国内黄色网址_久久久久亚洲精品国产 | 激情久久中文字幕_亚洲经典国产欧美_草草久久久_91看片儿_蜜臀免费av_美女一区视频_97在线视频免费看_内插射精大群交在线 | 一区动漫_国产91在线高潮白浆在线观看_72成人网_国产一女三男实拍视频_欧美最猛性xxxx_aaaaa一级片_国产高清一国产aV麻豆网_黄频网址 | 午夜男女爽爽影院免费视频_国产成一区二区_日韩视频第一区_亚洲韩日精品_26uuu久久综合_亚洲综合国产一区二区三区_免费中文字幕日韩_九九热免费在线 | 国内一区二区三区在线观看_亚洲中文字幕av无码专区_久久中文字幕无码A片不卡男同_18成禁人视频免费网站_亚洲欧洲精品专线_精品亚洲国产专区在线观看_欧美疯狂xxxxbbbb牲交_伊人色综合一区二区三区 | 成年人视频在线看_欧美久久性视频_超碰aⅴ人人做人人爽欧美_噜噜噜91成人网_亚洲欧美丝袜精品久久_国产精品成人无码A片免费网址_91一二区_91久久久精品国产一区二区蜜臀 | 嫩草黄色_69视频在线播放_亚洲精品mv在线观看_波多野结衣AV最新作品在线观看_国产视频精品视频_欧美肥婆丰满bbw_成人免费网视频_亚洲日本中文字幕网站 | 999免费观看视频_亚洲av无码专区亚洲av_老外一级黄色片_久久人妻少妇嫩草AV无码专区_日日夜夜视频_夜夜操女人_99啦porny丨首页入口_日本黄色性片 | 欧美在线视频一区_日本精品一区二区三区在线播放_日本熟妇人妻xxxx_又色又爽美女网站_亚洲AV无码成人精品区一区_做暖暖小视频免费xo_军人野外吮她的花蒂无码视频_亚洲中文字幕无码人在线 | 久久精品2_性色一区二区三区_久草热这里有精品6_天天爽夜夜爽夜夜爽_91麻豆国产福利精品_99精品视频精品精品视频_一级大片免费_久久99精品国产麻豆不卡 | 真实国产乱人伦在线视频播放_国产一区二区免费网站_青娱乐这里只有精品_亚洲国产天堂一区二区三区_久久第三页_精品熟人妻一区二区三区四区不卡_日本a片大尺度高潮无码_午夜视频在线观看一区 | 性做久久久久久久_97久久超碰国产精品最新_亚洲国产av无码精品果冻传媒_1000黄色片_美女露100‰奶头18禁_国内自拍99_亚洲人午夜_欧美XXXXX高潮喷水 | 麻豆911传媒_99在线精品视频在线观看_人人九九精_天天操天天射综合_特黄一毛二片一毛片_国产精品多久久久久久情趣酒店_久久综合给合综合久久_91久久精品亚洲中文字幕无码 | 新91在线观看_久久中文字幕亚洲精品最新_AⅤ无码国产在线看_久青草国产在视频在线观看_免费h片在线观看_国产精品美女视频免费午夜版_猫咪成人官网_成人免费午夜视频69影院 | 久久久久久臀欲欧美日韩_国产免费片_五月久久六月婷婷俺也去_久草在线欧美_一级片片_91大神精品视频_91麻豆精品国产91久久久_国产欧美精品 | 在线免费91_一级久久久久久_一本大道伊人av久久乱码_一级黄片一级毛片_大地资源网视频在线观看新浪_www久久99_成人无码区免费视频_国产全肉乱妇杂乱视频 | 亚洲在线高清_亚洲精品成人在线_黄色一级免费观看_天天澡天天揉揉av在线_欧美国产一区二区在线_国内精品久久久久影院网站_国产成人精品无缓存在线播放_91啦91丨porny丨论坛 | 精品国产亚洲第一区二区三区_高清国产在线观看_日本最新免费二区三区_a级片观看_亚洲一级不卡_国产呦VA在线观看_日韩人妻无码精品—专区_中国少妇嫖妓BBWBBW | 久久成人精品一区二区三区_中文字幕V亚洲日本在线_精品无码久久久久久久动漫_成年午夜无码AV片在线观看_91色精品_一个人看的视频www免费_国产肉丝袜在线观看_中文字幕av播放 | 日本精品区_国模私拍xvideos_亚洲gv白嫩小受在线观看_超碰人人在线_91日韩久久_国产欧美洲中文字幕_91久久_h纯肉无遮掩3d动漫在线观看 | 老赵揉着粉嫩的双乳小说_在线观看无码AV免费不卡软件_日日爽视频_久久蜜臀_免费大黄网站在线观_久热精品在线中文字幕播放_欧美一级理论性理论a_色婷婷综合久久久久中文一区二区 | 国产视频精品区_在线观看一级黄色片_国内自产少妇自拍区免费_九九精品网_精品视频一区在线观看_久久精品A片777777_国产精品网站一区二区三区_日本老妇xxxx | 黄色小说视频网_91桃色黄色_99久久精品无码一区二区三区_少妇人妻大乳在线视频_91精品专区_免费在线观看成人网_久久精品成人影院_精品亚洲一区二区三区四区五区高 | 好爽好紧好大的免费视频国产_亚洲欧美日韩久久一区二区_亚洲一级毛片免费看_国产午夜一级_成人3D动漫一区二区三区_成年免费视频播放网站推荐_FREE性欧美人与DOOG_国产成人精品免费久久久久 | 黄色特级视频_国产天堂久久_欧美の无码国产の无码影院_亚洲精欧美一区二区精品_美乳在线播放_久久精品日产第一区二区三区的功能_免费在线看成人av_高清一区二区视频 | 日韩中文字幕欧美_欧美伊人网_天天夜天天操_午夜爽爽爽男女免费观看hd_26uuu成人网_国产一国产aa毛片_不卡在线观看亚洲视频_日本人妻出轨中文字幕 | 国产精品99久久99久久久_欧美韩日精品_久久的久久爽亚洲精品aⅴ_善良的人妻被水电工侵犯_国产精品亚洲产品一区二区三区_日本欧美一区二区三区在线观看_久久久久国产亚洲AV麻豆_中国一级簧片 | av成人免费在线_色在线视频网站_国产ts视频_国内xxxx乱子另类_久久综合草_无码欧美熟妇人妻影院_九九热久久99国产盗摄蜜臀_色资源av | 亚洲中文在线精品国产_日本成人一级片_免费毛片一区二区三区久久久毛片_白浆在线播放_国产精品久久久久久久久网站导航_japan白嫩丰满少妇videoshd_亚洲成人h_bnb998成人免费 | 国产91足控脚交在线观看_午夜精品久久久久久久99热蜜臀_免费日p视频_亚洲人成无码网站_国产精品久久久久久久新郎_国产www在线_国产一女三男3p免费视频_久久久精品成人 久久成人精品一区二区三区_中文字幕V亚洲日本在线_精品无码久久久久久久动漫_成年午夜无码AV片在线观看_91色精品_一个人看的视频www免费_国产肉丝袜在线观看_中文字幕av播放 | 国产精品自在拍视频首页_中文字幕乱码亚洲无线码按摩_成人激情视频在线观看_www.四虎com_国产在线视频99_2002亚洲精品真实在线_国产精选在线播放_色先锋影音岛国av资源 | 麻豆911传媒_99在线精品视频在线观看_人人九九精_天天操天天射综合_特黄一毛二片一毛片_国产精品多久久久久久情趣酒店_久久综合给合综合久久_91久久精品亚洲中文字幕无码 | 欧美久热_欧美网站在线观看_免费日批视频_精品a在线_国产精品无码MV在线观看_一级黄色大片儿_国产中文字幕精品视频_久久成人一区 | 日本免费黄色_黄色网址在线免费看_传媒精选麻豆_久久久久久久99精品欧美产片_美女黄网站18禁免费看_精品免费国产一区二区_中国少妇初尝黑人巨高清_欧美伊人久久大香线蕉在观 | 成人无码A区在线观看视频_亚洲一二三四果冻传媒_欧美香蕉爽爽人人爽_伊人网91_极品国产91在线网站_丁香五月综合久久激情_亚洲在人线_精品一品国产午夜福利视频 | 久一精品视频_亚洲欧洲毛片_亚洲精品国产成人99久久6蜜臀_亚洲射逼_五月婷婷久久中文无码_91爱视频_樱花草在线社区WWW_护士巨好爽好大乳 |